Mais informações

KIMURA, Ken-ichi et al. Design features and measured results on the natural ventilation system with solar chimney and cool pit in a school building. In: CONFERENCE ON PASSIVE AND LOW ENERGY ARCHITECTURE, 20., 2003, Santiago do Chile. Anais... Santiago do Chile, 2003.
Clique no nome do(s) autor(es) para ver o currículo Lattes:

Dados do autor na base InfoHab:
Número de Trabalhos: 1 (Nenhum com arquivo PDF disponível)
Citações: Nenhuma citação encontrada
Índice h: Indice h não calculado  
Co-autores: Nenhum co-autor encontrado

Dados do autor na base InfoHab:
Número de Trabalhos: 4 (Nenhum com arquivo PDF disponível)
Citações: 1
Índice h: 1  
Co-autores: Nenhum co-autor encontrado

Dados do autor na base InfoHab:
Número de Trabalhos: Nenhum trabalho cadastrado(Nenhum com arquivo PDF disponível)
Citações: Nenhuma citação encontrada
Índice h: Indice h não calculado  
Co-autores: Nenhum co-autor encontrado

Dados do autor na base InfoHab:
Número de Trabalhos: 3 (Nenhum com arquivo PDF disponível)
Citações: Nenhuma citação encontrada
Índice h: Indice h não calculado  
Co-autores: Nenhum co-autor encontrado

Abstract

The design features and the results of a year round field measurement on the natural ventilation system with solar chimney and cool pit underneath the structure of a four storied school building of Kitakyushu University are described. The building design involves natural ventilation system, light shelves, photovoltaic system and light court. The natural ventilation system invites outside air through cool pit to be delivered into various indoor spaces and exhausted through the solar chimney on the roof for each division of eight blocks. The measured results for the first full year showed that the annual total outside air load reduction by natural ventilation system amounted to 30GJ in cooling and 60GJ in heating with less operating hours of natural ventilation than expected. The fresh air load was decreased by 6.4% of the total annual air-conditioning load of the school building.[Jp03]
-