Mais informações

Zhifeng, Xue; Feng, Chen; Yi, Jiang. VAV system analysis. In: BUILDING SIMULATION, 6., 1999, Kyoto. Anais... Kyoto, 1999. p. 925-930.
Clique no nome do(s) autor(es) para ver o currículo Lattes:

Dados do autor na base InfoHab:
Número de Trabalhos: 1 (Nenhum com arquivo PDF disponível)
Citações: Nenhuma citação encontrada
Índice h: Indice h não calculado  
Co-autores: Nenhum co-autor encontrado

Abstract

There are two kind of supply fan rotation speed control methods, one is the static pressure control method, the other is the float pressure control method. Simulation shows that they have different working point along the whole year. The supply air fan controlled with float pressure control method need low rotation speed and works on high efficiency, so the float pressure control method need only 30% fan operation energy of the static pressure control method. The layout of the air duct may influence the fan control method.
-